CFF 800

Fire Suppression Systems


The CFF 800 is one of our patented Dual Agent fire suppression systems. The CFF 800 utilizes a combination of CF-33 Dry Chemical and FM-200 Clean Agent gas to offer a 20% advantage over a similar sized dry chemical only unit. Each unit is built standard with a 155°F upright sprinkler head, Nason low pressure switch (for system monitoring or as a power shutoff), and an easy to read pressure gauge. Custom options for all of our units are available upon request.

The Cease Fire® System Unit CFF 800 must be hung vertically with the sprinkler deflector pointed downward. The unit is to be used in areas where the temperature falls between 32° degrees and 120° degrees Fahrenheit (0° to 48.89° degrees Celsius). The unit is to be mounted or attached to a secure ceiling, for example; wood, metal, or concrete. Insure there are no obstructions to the free flow operations of the sprinkler head and disbursement of the extinguishment within the enclosure.
Do not mount on suspended ceiling or loose tiles.

The Cease Fire® Unit is self-activating. Each unit is designed to initiate automatically by means of a sprinkler head rated at 155ºF (68ºC). Alternative temperature settings are available upon request. The temperature rating for each sprinkler head is stamped on the star shaped deflector in both Fahrenheit and Celsius measurements. The temperature of the sprinkler head is fixed and must be designated at the time of purchase. When the temperature rise to activate the Cease Fire® unit, the sprinkler head opens automatically and dispenses the entire contents in less than 10 seconds onto the fire and throughout the enclosure being protected. If the unit is equipped with the optional pressure switch, a signal is sent at the time of discharge to activate accessory equipment, such as an alarm.

Specifications

  • Maximum Total Flood Volume8.20’x8.20’x12.20′ = 820ft³ / 2.5mx2.5mx3.72m = 23.25m³
  • Reach Coverage Area 8.20’x8.20′ = 64.24ft² / 2.5mx2.5m = 6.25m²
  • Temperature Rating 32°F to 120°F / 0°C to 49°C
  • Cylinder Worthington
  • Diameter 7.50″ / 19.05cm
  • Height 11.38″+3.50″ Coupling Assembly /
  • 29cm+8.90cm
  • Capacity 16lbs / 7.26kg
  • Unit Weight 30lbs / 13.61kg
  • Ship Weight 32lbs / 14.55kg
  • Approvals UL, ULC, CSFM, NYC #5800
  • Propellant High Purity Compressed Dry Nitrogen
  • Standard System Activation: 155° Fahrenheit / 68.3° Celsius

Get a quote