CFCA 455 – 1200

Fire Suppression Systems


The Cease Fire® Unit is self-activating. Each unit is designed to initiate automatically by means of a sprinkler head rated at 155ºF (68ºC). The temperature rating for each sprinkler head is stamped on the star shaped deflector in both Fahrenheit and Celsius measurements. The temperature of the sprinkler head is fixed and must be designated at the time of purchase. When the temperature rise to activate the Cease Fire® unit, the sprinkler head opens automatically and dispenses the entire contents in less than 10 seconds onto the fire and throughout the enclosure being protected. If the unit is equipped with the optional pressure switch, a signal is sent at the time of discharge to activate accessory equipment, such as an alarm.

Specifications

  • Suppressing Agent: FM-200 Clean Agent Gas
  • Maximum Total Flood Volume: 900 Cu. Ft. / 25.49 Cubic Meters
  • Design Concentration: 7%
  • Temperature Rating/Validation: 32°F to 120°F / 0°C to 49°C
  • Cylinder: Manchester #11
  • Diameter: 12.25” / 31cm
  • Height: 10.5” + 3.50” Coupling Assembly / 26.67cm + 8.90cm
  • Capacity: 30.69 lbs / 13.92 kg
  • Unit Weight: 46.75 lbs / 21.21 kg
  • Ship Weight: 51.75 lbs / 23.48 kg
  • Operating Pressure: 175 psi / 1207 kPa
  • Propellant: High Purity Compressed Dry Nitrogen
  • Standard System Activation: 155° Fahrenheit / 68.3° Celsius
  • Designed and Tested by Cease Fire® in Accordance with NFPA-2001

Get a quote